FIREGUARD® DOUBLE-WALL ABOVEGROUND FUEL STORAGE TANK

FIREGUARD® FUEL STORAGE TANK

The FIREGUARD tank is designed to meet the UL 2085 standard, which specifically addresses the construction and performance requirements for protected aboveground tanks that are intended for the storage of flammable and combustible liquids. The FIREGUARD tank offers a higher level of fire protection that its FLAMESHIELD® counterpart, with a two-hour fire rating and double-wall steel construction with a unique lightweight thermal insulation layer in between that exceeds the UL two-hour fire test, providing enhanced protection against leaks, spills, and fire exposure.

Eaton Sales & Service constructs FIREGUARD tanks to meet and exceed all the requirements set forth by the UL 2085 standard for fire-resistant tanks.

A FIREGUARD® UL 2085 aboveground fuel storage tank manufactured by and waiting to be shipped from Eaton Sales & Service's yard.

Why This Above Ground Tank?

The FIREGUARD® tank is designed to provide a high level of fire and impact protection with a two-hour fire rating, ensuring that the double-wall steel tank can withstand exposure to a fire without releasing its contents. The insulating material between the steel layers is 75% lighter than concrete, reducing shipping, installation and relocation costs.

FIREGUARD® TANK BENEFITS

  • Fire Protection: The FIREGUARD tank is designed to provide a high level of fire protection with a two-hour fire rating, ensuring that the tank can withstand exposure to a fire without releasing its contents.
  • Double-Wall Construction: The tank features a double-wall design with an outer steel wall and an inner thermally insulated steel wall, providing secondary containment and protection against leaks and spills.
  • Environmental Safety: The double-wall construction and secondary containment of the FIREGUARD tank help prevent leaks and spills, ensuring environmental safety and compliance with regulations. Steel construction allows for recycling.
  • Versatility: The tank is available in various sizes and configurations to suit different storage needs, making it suitable for a wide range of applications, including retail and commercial fueling centers.
  • Longevity: Constructed with high-quality materials and designed to withstand harsh conditions, the FIREGUARD tank offers durability and a long service life.
  • Compliance: The tank meets UL-2085 standards, which are widely recognized in the industry as ensuring the highest level of safety and quality for aboveground storage tanks.
  • Peace of Mind: Choosing a FIREGUARD tank provides companies with the confidence that their fuel storage needs are met with a tank that offers superior protection, durability, and compliance with industry standards.
2 FIREGUARD® double-wall aboveground tanks behind a security fence with a platform manufactured and installed by Eaton Sales & Service.
Two FIREGUARD tanks storing MOGAS and DIESEL at this remote fueling site.

REQUEST A QUOTE!

FIREGUARD® TANK FEATURES

Eaton Sales & Service can build the FIREGUARD tank in a variety of sizes and configurations.

  • Ballistics and impact protection per the UL-2085 standard.
  • Steel inner tank with another steel secondary tank for containment that adds strength, security and is easily recycled.
  • The outer steel tank is impermeable and crack resistant and encloses a specialized concrete (a lightweight monolithic thermal insulation material) that is part of a patented process resulting in a lighter material weight than concrete alone.
  • Secondary containment is testable on-site using standard, economical testing procedures.
  • Meets National Fire Protection Association (NFPA) 30 and 30A International Fire Code (IFC) requirements.
  • Interstitial space can be monitored for leak detection.
  • Compatible with a wide range of fuels and chemicals, including biodiesel and ethanol.
Anatomy diagram of the double-wall design of a FIREGUARD fuel storage tank.
Anatomy of the double-wall design with the thermal insulation of a FIREGUARD aboveground fuel storage tank

FIREGUARD® TANK SPECIFICATIONS

These specifications are for a cylindrical design and shown are outer tank dimensions. Rectangular designs are also available upon request.

NOMINAL GALLONSDIAMETER (inches)LENGTH (inches)EST. WEIGHT (LBS)
18648541,750
25048682,100
30050722,350
50060763,100
56060843,350
1,00070783,800
1,500701145,500
2,000701506,500
2,500701867,900
3,000702229,000
4,0009017412,300
5,00010216813,750
6,00010219815,500
8,00010225820,000
10,00010233024,500
12,00010239028,000
15,00012631234,500
20,00012641439,500
25,00012651649,000
30,00012661874,000
FIREGUARD aboveground fuel storage tank specifications